KNX lighting, shutters and blinds with Link’nX: Shelly, Somfy

Link’nX connects lighting, shutters and blinds to the KNX bus in two ways: integrated devices, such as Shelly relays, covers and lights or the shutters and blinds of a Somfy box, and the KNX actions and triggers of scenarios. This page helps you choose the path according to the device and the need.

NeedApplicationGuide
Control a Shelly relay, cover or light from KNXLink’nX, Shelly gatewayMap Shelly relays, covers and lights to KNX
Read a Shelly’s state, power or position on the busLink’nX, second tab of the Shelly gatewayRead Shelly feedback
Open, close or position a Somfy shutter or blind from KNXLink’nX, Somfy gatewayMap Somfy commands and states to KNX
Control a Somfy device in a scenarioLink’nX, Somfy actionsControl a Somfy device
Start a scenario on a Somfy state, such as a closureLink’nX, Somfy triggersTrigger a scenario on a Somfy state
Write values to one or more group addresses in a scenarioLink’nX, KNX actionsPrepare a KNX action
Start a scenario on a KNX telegramLink’nX, KNX triggersCreate a KNX trigger

Each device path starts with its declaration: a Shelly device with its IPv4 address and port, or a Somfy box whose discovered devices must be saved.

  • Shelly has no dedicated action type or trigger: to use it in a scenario, create a KNX action with the address, DPT and value of its mapping.
  • Shelly covers: open/close in DPT 1.008, where 0 opens and 1 closes; set position in DPT 5.001, where 0 = open and 100 = closed.
  • A Shelly toggle in DPT 1.017 inverts the state on each telegram, including at 0: a button that sends on press and on release can toggle twice. Setting a light’s brightness is not enough to switch it on either.
  • For a Gen1 Shelly cover or dimmer, have the path validated by support@can-nx.com before relying on its commands and feedback.
  • Somfy: position setpoints are expressed as a percentage from 0 to 100 in DPT 5.001, and a setpoint of 0 is not the Stop command. For a standard KNX shutter push button, map Up / down (KNX button) in DPT 1.008: Open and Close only react to the value 1.
  • A KNX trigger reacts to a write matching the configured address and value; a simple status read does not trigger it.

Brand pages: Shelly and Somfy. To build scenarios, see Scenarios and commands.