Skip to content

KNX EV charger integration: Evlink, Lektri.co, Terra AC with Can’nX

Can’nX connects three EV charger models to the KNX bus and to energy management: Evlink Pro AC, Lektri.co and Terra AC. In Link’nX, the charger declared by its IP address receives commands from KNX group addresses or scenario actions, and its states and measurements can be mapped to KNX addresses. In Emergy’nX, it joins IRVE monitoring and optimization: off-peak hours, solar surplus, distribution between chargers.

NeedApplicationGuide
Declare an Evlink Pro AC, Lektri.co or Terra AC charger on the gatewayLink’nX, Devices → Climate & EnergyDeclare an EV charger
Start, stop, suspend or limit charging from KNX, depending on the modelLink’nX, charger gateway, Actions tabAssociate the KNX commands of a charger
Read the vehicle state, currents, power or energy on the busLink’nX, second tab of the gatewayRead KNX feedback and troubleshoot a charger
Control a charger in a scenarioLink’nX, Evlink Pro AC, Lektri.co or Terra AC actionsPrepare a charger action
Monitor charger power and its share of the building’s consumptionEmergy’nX, IRVEMonitor EV chargers
Configure the charger, its intensities and its optimization optionsEmergy’nX, Equipment → Add EquipmentConfigure an EV charger
Force on or off, return to automatic or send a setpoint in amperesEmergy’nX, Dashboard → Equip.Choose Auto, OFF or ON and send a custom value

In Emergy’nX, a charger of another model is configured with the Other type and its KNX links: active power, intensity, vehicle connection status and commands.

  • Current limits are expressed in amperes, not kW, in DPT 14.019 on the KNX side; 6 to 32 A for Evlink Pro AC. To stop charging, use the stop command: a setpoint of 0 or below 6 A does not replace it.
  • The KNX Stop charging, Start charging, Suspend charging or Lock socket rows (DPT 1.001) are distinct commands: do not treat a write of 0 as cancelling them.
  • Lektri.co pause, resume, reset and schedule override are in the KNX gateway, not in the actions. To run an Evlink Pro AC or Lektri.co action from a scenario, first have the path confirmed by support.
  • Vehicle state (Evlink), Charging state (Terra AC) and Charger state (Lektri.co) are status codes, not a battery level.
  • In Emergy’nX, both intensities accept values from 6 A. With Managed, Overload protection and Balancing between chargers are always active; Charge anytime has an exception on Tempo red days.
  • On the IRVE dashboard, a charger’s percentage is its share of total IRVE power, not the charging progress.

Applications involved: Link’nX and Emergy’nX. For the building’s load shedding and tariffs, see Energy and metering.