Skip to content

Create an Evlink Pro AC, Lektri.co or Terra AC charger action in Link’nX

Link’nXAdministratorInstaller

Link’nX web: Actions in the AUTOMATION section, Evlink Pro AC, Lektri.co and Terra AC types

A Link’nX charger action sends a command to an Evlink Pro AC, Lektri.co or Terra AC EV charger: start, stop or suspend charging, limit the current in amperes or lock the socket, depending on the model. Once saved, it can be added to a scenario. To control the charger directly from the bus, use its KNX commands instead.

Intended for authorized administrators and installers.

  • The charger is declared in the right gateway.
  • The current limits authorized for the installation are known.
  • For a scenario to run an Evlink Pro AC or Lektri.co action in your installation, first have the path confirmed by support, before relying on the automation. For Terra AC, follow how to compose a scenario.
  1. In the AUTOMATION section of the sidebar, open Actions and click Add.
  2. In Select an action type, choose Evlink Pro AC, Lektri.co or Terra AC.
  3. Fill in the required Name: at most 64 characters, including at least one character other than a space. Fictitious example: “North charger limit”.
  4. Select the charger in Evlink Pro AC device, Lektri.co to control or Terra AC to control. Start with a single identified charger. For a Lektri.co command targeting several chargers, have the path confirmed by support before relying on a collective result.
  5. Choose the command in Evlink Pro AC command, Lektri.co command or Terra AC command, using the tables below.
  6. When Value appears, explicitly enter the appropriate value. Do not keep the initial value without checking its meaning and the installation’s limits.
  7. Click the floppy-disk icon at the bottom right and wait for Success!.
Displayed commandUse
Modify the maximum charging powerA current limit in amperes: an integer from 6 to 32 A, within the limits authorized for the installation. For example, 16 means 16 A, not 16 kW
Stop ChargeStop the ongoing session
Suspend ChargeSuspend the ongoing session
Restart ChargeResume a suspended session; it is not used to start a new session
Reboot the stationRequest a restart of the station
Set to “Available”Request the available status
Set to “Unavailable”Request the unavailable status; according to the help, a charge in progress finishes before this change

Only the first command asks for a Value; the others ask for no number. To stop charging, choose Stop Charge: a limit of 0, a negative value or a value below 6 does not replace it.

CommandLektri.coTerra AC
Start chargePresentPresent
Stop chargePresentPresent
Set max currentValue in amperes: a positive integer confirmed for the installationValue in amperes, suited to the installation’s limits
Lock / UnlockNot in this listAct on the locking of the cable socket

For Terra AC, make sure no charging session is in progress before requesting unlocking. Do not confuse cable locking with starting or stopping a charge.

With Set max current, the form refuses 0 and displays Issue with value field. You need to enter a value. To stop charging, choose Stop charge. For a specific need for a zero setpoint, have the method confirmed by support: the action and the KNX association are not interchangeable.

The Lektri.co functions Pause charging, Resume charging, Reset device and Override charging schedule are in the KNX gateway table, not in this list of commands. Changing the interface language does not make them appear.

  1. Find the action in the list and open Edit. Review the name, the charger, the command and any value.
  2. Success! confirms that the action is saved, not that a command was transmitted or that the vehicle reacted. Distinguish saving, execution of the automation and the observed result.
  3. For a Terra AC action, add it to a scenario by following how to compose a scenario. After an authorized test, check the result on the charger and in the charger feedback.

Open Edit on the action. Its type cannot be changed in this mode. After the floppy disk, if a window lists the affected scenarios, review them, then choose SAVE to confirm or CANCEL to not apply the change. Duplication and the common confirmations are described in the action editing guide.

  • Type missing from Select an action type: check the context and the option for the family concerned. A charger present in another gateway is not enough.
  • Charger missing from the selection list: check its declaration in the same gateway and the action’s family. A Lektri.co charger cannot be selected in a Terra AC action.
  • Value refused by the form, or an Evlink limit needed outside the 6 to 32 A range: contact support.
  • Save succeeds with no effect on the vehicle: reopen the action and check the fields above. For Evlink Pro AC or Lektri.co, have the scenario path confirmed by support. To diagnose statuses and limits, see the charger feedback.

If these checks have already been done, write to support@can-nx.com, summarizing the product, the action, the charger, the value, the expected result and the tests carried out.

French labels: Sélectionner un type d’action, Nom, Equipement Evlink Pro AC, Commande Evlink Pro AC, Lektri.co à contrôler, Commande Lektri.co, Terra AC à contrôler, Commande Terra AC, Valeur. Evlink commands: Modifier la puissance de charge maximale, Arrêter la charge, Suspendre la charge, Reprendre la charge; Lektri.co and Terra AC: Lancer la charge, Arrêter la charge, Régler le courant maximum; Terra AC: Verrouiller, Déverrouiller.