Link’nX web: KNX gateway table of a declared EV charger, feedback tab

The second tab of the Link’nX gateway table maps KNX group addresses to the feedback of an Evlink Pro AC, Lektri.co or Terra AC EV charger: vehicle and charging status, current, voltage, power, energy, cable locking and error codes. The tables below give the DPT of each feedback and the meaning of the status values, followed by the checks to run when charging does not go as expected.

Intended for installers and administrators who configure feedback, and for authorized users who interpret the displayed information. Always check which charger, which function and which observation time are concerned.

  1. In the right project and gateway, open Devices → Climate & Energy, then Evlink Pro, Lektri.co or Terra AC.
  2. On the charger’s row, click the two opposing arrows, Gateway mode configuration.
  3. Open the second tab, marked with a message bubble. Check the function name and its DPT in the tables below.
  4. Fill in its KNX group Address and tick Active if this feedback must be used.
  5. Save with the floppy disk and wait for Données sauvegardées avec succès ! (Data saved successfully!). Then reopen the table to check the values, as described in the gateway table guide.
Displayed feedbackDPT
Vehicle state, Last stop cause5.010
EV presence1.002
Current L1, Current L2, Current L314.019
Voltage L1, Voltage L2, Voltage L314.027
Total active power, Total apparent power14.056, 14.080, respectively
Power factor, Frequency14.057, 14.033, respectively
Total active energy, Session energy13.010
Total reactive energy13.012
Contactor charging time, Session charging time12.100

Vehicle state is a numeric status, not a battery percentage. The documented values notably distinguish 2 available not ready, 3 vehicle connected not ready, 6 available ready, 7 vehicle connected ready, 8 charging and 9 charging with ventilation required. 4 and 5 correspond to a stop request in the charging states concerned. 0, 1, 10 and 11 describe other states of the control pilot signal: do not draw a hardware diagnosis from them without confirmation, and send the value and its context to support if the status is unexpected or unknown.

Last stop cause concerns the last session or the rejection of its start, not necessarily an error that is still active: 0 no cause given, 1 emergency stop, 2 vehicle disconnected, 3 hardware reset, 4 local command, 5 other, 6 power loss, 7 reboot, 8 remote command, 9 software reset, 10 unlock command, 11 not authorized. Report an unexpected value to support without inferring the current cause from it.

Before programming a condition on EV presence, have support confirm the 0/1 mapping for your installation: the polarity cannot be inferred from the label alone.

For Total active power and Total apparent power, have the unit and scale expected by your display confirmed before any calculation or comparison. Do not assume an automatic conversion between W and kW, or between VA and kVA, based on the row name.

Displayed feedbackDPT or useful unit
Charger state, Extended charger state, Firmware version16.001, text
Session charged energy, Energy index, Total charged energy13.010; the session is expressed in Wh
Session charging time12.100, seconds
Session ID, Heap free space12.001; these are not power measurements
Instant power14.056, W
Current, Current phase 1, Current phase 2, Current phase 3, Install current, Dynamic current, Load balancing current limit, PWM current value14.019, A
Voltage, Voltage phase 1, Voltage phase 2, Voltage phase 314.027, V
Temperature9.001
Current limit reason, LED brightness5.010
Headless flag, Active errors flag, Charger paused flag1.001

Charger state returns a letter, from A to F according to the IEC 61851 standard, as stated in the row’s help. Extended charger state notably distinguishes A (vehicle disconnected), B (connected), B_AUTH (waiting for authentication), C (charging), D (charging with ventilation required), E (error), OTA (update), LOCKED (charger locked), B_PAUSE (pause) and B_SCHEDULER (pause due to the schedule). These texts are specific to Lektri.co: do not convert them into a Terra AC or Evlink status number.

Current limit reason distinguishes: 0 hardware capabilities, 1 installation limit, 2 user limit, 3 dynamic current, 4 schedule, 5 offline energy management, 6 energy management, 7 OCPP current. Read this feedback before changing a setpoint. It indicates the reason reported by the charger, without a procedure for changing these settings.

Current is not the sum of the three phases: use the phase feedback to distinguish them. Likewise, distinguish Dynamic current, Install current and Load balancing current limit. The availability of measurements depends on the information provided by the charger; a missing measurement is not a zero value.

Displayed feedbackDPT
Charging state, Socket lock state5.010
Charging current limit (A), Current L1 (A), Current L2 (A), Current L3 (A), User settable max current14.019
Active power (W)14.056
Voltage L1 (V), Voltage L2 (V), Voltage L3 (V)14.027
Energy delivered (Wh)13.010, session energy
Error code7.001; do not reduce it to a byte

Charging state: 10 idle, 20 vehicle plugged in waiting for authorization, 21 ready to charge, 30 vehicle ready without PWM, 40 charging at nominal current, 41 charging below the commanded value, 50 other state and 99 unknown. This feedback does not indicate the vehicle’s battery percentage. 41 signals limited charging, not necessarily a fault.

Socket lock state: 0 no cable; 1 cable on the charger side, unlocked; 2 cable on the charger side, locked; 3 cable connected to the charger and the vehicle, unlocked on the charger side; 4 connected to both and locked on the charger side; 99 unknown. To know whether a charge is in progress, read Charging state: the cable status alone is not enough.

For Error code, use the manual for the model or send the exact code to support. The number alone gives neither a component diagnosis nor a repair procedure. According to the row’s help, User settable max current is set with the Terra Config app, whose steps and setting limits are not described here; have them confirmed if needed.

Check the feedback obtained on your installation’s viewing device. The gateway table configures the associations; its rows do not show the charger’s measurements live. Only a value read on this device shows that a measurement is received; a missing value is not a zero value.

  • No feedback: check the gateway, the charger’s declaration, the feedback tab, the address, the DPT, the Active box and the save. Then check that the viewing device actually requests the associated feedback. Do not present missing data as 0 or as a stopped charge.
  • Vehicle connected but not charging: compare the charging status, the pause or the schedule and, if available, the limitation reason. A start request, a locked socket or a saved current limit must always be checked by observing the result. For an Evlink Pro AC or Lektri.co scenario command, have the path confirmed by support.
  • Charging lower than expected: distinguish the setpoint, the current actually measured and the various limits displayed. Do not raise a limit just to make the symptom disappear.
  • Status or error code not understood: note the exact value, the function and the observation time, then contact support.

If the checks have already been done, write to support@can-nx.com with the family and model if known, the gateway, the function and its DPT, the exact value or message, the observation time, the expected result and the checks already carried out. Add a screenshot without sensitive data if it helps; never send a password, key or private log.

French labels: État du véhicule, Présence du véhicule and Cause de l’arrêt de la dernière session (Evlink), État du chargeur, État du chargeur étendu and Raison de la limite de courant (Lektri.co), État de charge, État du verrouillage de la prise and Code erreur (Terra AC).