Link’nX web: Actions and Scenarios lists, launch button and activation

The play triangle in the Link’nX lists immediately runs an action or a scenario’s sequence, without waiting for its trigger. For a KNX action, you can send the configured value or test a custom value.

Intended for administrators and installers authorized to work on the equipment of the Link’nX context. These commands request execution on the installation: first check the project, the gateway, the target equipment and the planned actions. Do not use them simply to make a configuration warning disappear.

  1. In Actions, find the action and check its configuration. Exit Select if its buttons are hidden.
  2. Click its play triangle on the right, whose tooltip is Launch action sequence.
  3. For a KNX action, choose Test with default value to request the configured value, or Enter custom value for a test with a known value suited to the equipment.
  4. If you chose Enter custom value, the Custom value window opens. Fill in Value, then click Ok. Cancel closes this window without requesting the test.
  5. Wait for Action is running.

In the Custom value window, the initial value shown is 0: do not confirm it without checking that it suits the intended data type and command. For an action of a type other than KNX, the triangle directly requests execution with the configured value.

In a scenario’s form, the triangle in a circle, to the right of an action card, also requests an immediate test of that single action, without waiting for its delay: see setting a scenario’s sequence.

  1. In Scenarios, find the row. If necessary, view its composition to know the action sequence and its delays.
  2. Click the Launch action sequence triangle on this row. This request does not present the custom value form of KNX actions.
  3. Wait for Scenario is running!.

A scenario’s switch changes its activation state. After toggling it, wait for Updated! and check the displayed state. Activation and the launch triangle are two separate commands.

An execution already requested is not canceled by closing the page. Do not rely on a second click or on disabling the scenario to reverse commands already carried out. To establish precisely how a manual launch handles conditions, a disabled scenario or a sequence already in progress, or for a stop or resume behavior that is not established in your configuration, contact support before a test whose result could be undesirable.

  • After Action is running or Scenario is running!, check the expected observable result on each device: the message indicates that execution is requested, the device shows whether it took place.
  • For a scenario, view the scenario history if useful. Take the configured delays into account before launching again.

For The test could not be performed, or if the expected result is not observed:

  1. Check the context, the selected action and its known parameters.
  2. For a scenario, check the name and time in the history.
  3. Do not click the launch button repeatedly to diagnose a lack of response.

If these checks have already been made, contact support@can-nx.com with the product, the gateway, the action or scenario, the time, the message and the observed result.