Pool’nX KNX group monitor and telegram logging on SD card
Pool’nXAdministratorInstaller
Pool’nX local configuration site: KNX Group Monitor and KNX Datalogging
The local configuration site of the Pool’nX shows the KNX bus telegrams live, sends reads and writes to a group address and displays the history of the telegrams recorded on the SD card.
Intended for the integrator who tests the pool addresses or looks for a past telegram, without starting ETS. To open the site, follow signing in to the local configuration site.
Before you start
Section titled “Before you start”- You are signed in to the local configuration site of the gateway.
- The browser supports WebSockets, which the group monitor needs.
- For the history, an SD card is inserted in the SD CARD reader on the front panel: see Pool’nX wiring.
Follow the telegrams live
Section titled “Follow the telegrams live”- In the menu, open KNX Group Monitor.
- Check that WebSocket status : shows Open. The telegrams are listed with No., Time, Service, Priority, Source, Destination, Route and Value.
- Tick Group addressed and Physically addressed to show one or the other type of destination, and choose 2-Stage or 3-Stage for the display of group addresses.
- To see only certain addresses, enter a pattern in Filter, for example 1/2/3 4/2/* !1/2/5 (example).
- Untick Scroll to freeze the list while you read it; tick Raw Data to show the bytes received. Clear table clears the displayed list.
Busload:, Repeated: and Busvoltage: give the bus load, the repeated telegrams and the bus voltage.
| Filter pattern | Effect |
|---|---|
| 3 | Level equal to 3 |
| 2-7 | Level between 2 and 7 |
| 1,3,5 | Level equal to 1, 3 or 5 |
| * | The whole level |
| 1/2/* | The whole 1/2 group |
| 1/2/3 4/5/6 | Either address: several patterns combine with OR |
| 1/2/* !1/2/5 | The whole 1/2 group except 1/2/5: a pattern prefixed with ! excludes |
Physical addresses are written with dots, for example 1.1.10. An empty filter shows everything.
Read or write a group address
Section titled “Read or write a group address”- In the send row, enter the address in Group, for example 5/1/7 (example).
- Click Read to request the value: the response appears in the telegram list.
- To write, choose the Type, from 1Bit to 14 Byte string, enter the Value, then click Write. With n Byte, enter the bytes in decimal, separated by spaces.
- To repeat the write, tick Cyclic, enter the interval in Seconds, from 0.1 to 60, then click Write. To stop it, untick Cyclic and click Write again, or leave the page.
The + button adds a send row for another address.
A write is sent on the KNX bus and controls the devices concerned, including the pool if the address is a Pool’nX command. Test on an address whose effect you know.
View the telegram history
Section titled “View the telegram history”- Open KNX Datalogging.
- At the top of the page, check the recording medium: Datalogger on SD-Card with the total and free space of the card, or Datenlogger internal/SD-Karte (recording on the built-in memory, eMMC).
- Fill in From and To, date and time, or click Last 24h.
- Fill in the number of Rows, 10000 by default, and if needed a pattern in Filter, with the same syntax as the group monitor.
- Click Data request. More.. loads the next rows; Clear table clears the displayed list.
- Click Download to file! to save the telegrams of the period in a text file.
The download only takes positive patterns into account: an exclusion prefixed with ! only applies to the displayed list.
At 3 telegrams per second, that is a bus load of 10%, logging takes up about 2 GB per year.
Check the result
Section titled “Check the result”- Pressing a KNX push-button of the installation appears immediately in the group monitor, with its source and its value.
- After Read, the response of the device appears in the list.
- The history of a known period contains the expected telegrams.
Troubleshooting
Section titled “Troubleshooting”| Message or symptom | Cause and action |
|---|---|
| WebSocket status : Closed | The monitor is not connected to the gateway. Reload the page and check that the browser accepts WebSockets. |
| WebSocket not connected when sending | The read or the write was not sent. Wait for Open, then send again. |
| No telegram displayed | Check the filter, and that Group addressed or Physically addressed is ticked. |
| No SD card detected. Insert an SD card to record data. | No telegram is recorded. Insert an SD card in the SD CARD reader. |
| Data is currently being recorded on internal memory (eMMC). Inserting an SD card is recommended — it is more reliable for data logging. | Insert an SD card: it is more reliable for continuous logging. |
| Failed to load data | The gateway did not return the history. Shorten the period or reduce the number of Rows, then try again. |
For other situations, see Pool’nX troubleshooting. If the problem persists, write to support@can-nx.com with the gateway name, the page concerned and the message displayed.