Emergy’nX general meter: calculated or measured total consumption
Emergy’nXAdministratorInstaller
Emergy’nX, Building Config: General Meter card, total consumption method
The General Meter card in Emergy’nX defines how the building’s total consumption is obtained: by calculation, or by reading a dedicated meter over KNX or Modbus. The grid connection measurements and its tariffs are configured in the Power Network card, described in the Power network guide.
For the installer or administrator in charge of measurements, with the meter data provided by the installer.
Choose the method and fill in the meter
Section titled “Choose the method and fill in the meter”- In the project concerned, open Building Config, then Configure, or Edit, on the General Meter card. On a small screen, first open the three-line menu.
- In Total Consumption Method, choose the method planned for the installation:
| Option | How it works |
|---|---|
| Total of PV + Battery + Grid | The total adds up photovoltaic production, battery and grid. No meter field appears. These measurements must be correctly configured and available: see the Production and storage guide. |
| Value from on-site meter | The total is read from a dedicated meter, filled in at steps 3 and 4. Choose this option only if the dedicated measurement exists: the calculation does not require you to create a fictitious address. |
- For an on-site meter, choose the Phase type in Meter Settings: Single Phase or Three Phase.
- In Readings, choose the source of the Active Power measurement, KNX or Modbus; only the selected source is saved. With KNX, fill in the group Address and the DPT validated by the installer; the DPT suggested by default is 14.056. With Modbus, choose the measurement in Catalog value, then its unit, W or kW: the list shows the values declared for the project’s gateway, for example in the Chart’nX Modbus catalog.
- Click Save at the bottom. Wait for Configuration saved successfully; the form stays open.
Check the result
Section titled “Check the result”Go back to Building Config, reopen General Meter → Edit and reread the method, then the source, the address and the DPT or the Modbus value. The success message confirms that the parameters are saved: then check the real measurement on the dashboard of the same project. The gateway reads a Modbus value every 60 s.
Troubleshooting
Section titled “Troubleshooting”| Symptom | Checks |
|---|---|
| The meter fields do not appear | They only appear with Value from on-site meter. |
| The total seems incorrect | First check the project and the saved method. In meter mode, have the dedicated measurement and its DPT checked. In calculation mode, check the production, battery and grid indications, without changing the signs or the addresses at random. |
| No success message, or Configuration save error | Reread the form errors, then reopen the card to see what was kept. |
If these checks do not succeed, contact support@can-nx.com with the chosen method, the observed value, the expected result and the attempts already made.