Configure the L1, L2 and L3 phases of a three-phase Chart’nX meter

Chart’nXAdministratorInstaller

Chart’nX: energy generator in a three-phase installation, main meter cards

In a three-phase installation, the Chart’nX energy generator can read a meter phase by phase: a KNX group address or a Modbus configuration for L1, L2 and L3, with a total measured separately or calculated from the phases. This setting does not change the physical wiring.

For installers or administrators in charge of the configuration.

  1. In Main meters, enable the relevant card and choose the protocol according to the table below.
  2. In Measurement, select Per phase. The L1, L2 and L3 rows appear.
CardPhasesTotal choice
General meters - Apparent powerKNX or ModbusNo: the total measurement is still required in addition to the phases
General meters - Total energy consumedKNX or ModbusYes
PV meter and Grid meterKNX or ModbusYes
Battery meterKNX onlyYes; the dedicated total keeps the Group address label

Ordinary energy submeters and the water generator do not offer this per-phase configuration block.

  1. In KNX, fill in the address of each phase. The format has three levels: first number from 0 to 31, second from 0 to 7, third from 0 to 255. Fictitious example: 1/2/3.
  2. In Modbus, choose for each phase the matching configuration from the catalog. The U identifiers and R registers help to recognize the configurations.
  3. To add an old KNX address to a phase, click its small clock button with +, tooltip Add historical address, then fill in the new Historical row. An added historical row must be filled in; its cross removes it.
  1. If Total is offered, choose Dedicated address for a total measurement provided separately by the meter, or Sum L1+L2+L3 to calculate the total from the phases. The sum hides the total measurement field.
  2. With Dedicated address, also fill in Measured total address. The General meters - Apparent power card keeps this total measurement in addition to the phases and does not offer the sum.
  3. Check the units and the Index or Not indexed mode according to the meter fields. In Per phase mode, the meter unit applies to the L1, L2, L3 addresses and to the total.
  4. Save the dashboard.

Total returns to the overall measurement. Per-phase configuration preserved indicates that the phase addresses remain stored while their view is inactive: reread them when you reactivate Per phase. After a protocol change, check all the fields, as the same values are not necessarily kept.

After saving, open the per-phase panels and compare each phase with the measurement expected on the installation. If a phase stays empty or inconsistent, reread its address and the meter unit.

  • A warning symbol next to a KNX phase, with the tooltip Address already used by another phase or as historical, flags an address conflict to examine. It does not prevent saving: check the match with the installation before changing an address. Do not replace an address with a fictitious value to make the warning disappear.
  • The Measurement choice is missing: check the installation type, the card and the protocol.

For other symptoms, follow the meter troubleshooting. If the flow is still different, contact support@can-nx.com with the card, the protocol and the installation type.