In Boss’nX, a Modbus gateway describes a shared Modbus TCP access: its IPv4 address, its port and the CannX gateway that must reach it. It is then used by the components’ Modbus datapoints and by the metering configurations of the data logging.
Intended for administrators and installers. To duplicate, disable or delete a gateway, follow Modbus gateway management.
Before you start
Section titled “Before you start”- Your role has the Manage Modbus right. A viewing account is not enough.
- The installation’s parameters are confirmed: IPv4 address, Modbus TCP port and the CannX gateway that must reach this access.
- For an existing entry, check the uses concerned before editing it: a gateway can be shared by Boss’nX datapoints and metering configurations.
Open the form
Section titled “Open the form”- Open the supervision you want, directly or from hypervision.
- On a computer, choose Menu → Modbus gateways, in the Integration family; if it is folded, click its title first.
- To add an entry, click New gateway above the list. The form appears on the right.
- To edit an entry, click its row on the left: the Edit gateway panel shows its parameters. Check the name before making any change.
If a form is already open and you want to start another creation or a duplication, first click Cancel, then open the action you want. Cancel discards the pending changes; after Save, going back to the old parameters requires a new edit followed by a save.
Fill in the address, the port and the CannX gateway
Section titled “Fill in the address, the port and the CannX gateway”| Field | Value to provide |
|---|---|
| Name | A non-empty label that lets you recognize the access, for example Test boiler room, a fictional example. |
| IP Address | The confirmed IPv4 address of the Modbus TCP access, without spaces. A host name is not accepted instead of this address. |
| Port | An integer from 1 to 65535. Creation suggests 502; keep or change this value according to the actual configuration. |
| CannX Gateway | The gateway planned by the installer. The options show its name and its MAC. Check this choice even if a first option is already suggested. |
| Enabled | Check according to the planned use. The consequences of disabling are described in Modbus gateway management. |
The CannX Gateway list offers the project’s CannX gateways, whether they are online or not. If no CannX gateway is offered, have the project and its attachment checked rather than choosing another device at random.
Save the gateway
Section titled “Save the gateway”- Click Save.
- Wait for Saved successfully. and for the form to close.
To abandon before saving, click Cancel. To correct a value that has already been saved, reopen the entry, change the field you want and save again.
Check the result
Section titled “Check the result”- Find the entry in the list, then click its row to review the name, the address, the port, the CannX gateway and Enabled.
- Saving the parameters does not test communication with the hardware: then check that the associated datapoints or configurations work, following the installation’s procedure.
Declaring the gateway creates no datapoint. To use it in a component, then add a Modbus datapoint. To define the measurements to read on this access, follow the Modbus data logging configurations.
Troubleshooting
Section titled “Troubleshooting”| Message | Action |
|---|---|
| This field is required. | Fill in the missing name or CannX gateway. |
| Invalid IP address. | Check the four numbers of the IPv4 address and remove the spaces. |
| Invalid port (1–65535). or a browser validation refusal | Enter the confirmed integer port, within this range. |
| You don’t have permission to view this page | Have the Manage Modbus right checked on your role. |
| Error while saving. | Note the message and the fields concerned. Check the list before trying again. |
If the Modbus gateways entry is missing from the Menu, check the same right, the supervision context and the Integration family, which may be folded.
If the save seems to have succeeded but the row is missing, first clear the list’s search, then leave and reopen Modbus gateways. Do not immediately recreate an identical entry.
If the situation remains uncertain, contact support@can-nx.com with the supervision, the entry name, the message and your attempts. No password or private link is needed.
French labels: Menu → Passerelles Modbus, Intégration, Nouvelle passerelle, Modifier la passerelle, Nom, Adresse IP, Port, Passerelle CannX, Activée, Enregistrer, Annuler, Enregistré avec succès.